COMPRESSOR:
The unit shall contain hermetic
or semi-hermetic compressor(s) from the
best manufacturer. The semi- hermetic
compressor shall be the serviceable type,
and shall have an oil sight glass. The
compressor protection system shall include
over- current relay(s), dual pressure
switch (s), timer relay(s), oil pressure
switch(s) and internal thermostat(s) embedded
in the motor winding.
CONDENSER:
The Air-cooled condenser shall
be offin tube type construction. Imported
seamless copper tubes with high heat transferfins,
shall be expanded to tube.
The refrigerant circuits of the condenser
shall be cleaned and tested for leakage
at the maximum permissible working pressure.
COOLER:
The cooler shall be the dry expansion
type horizontal shell and tube type within
welded steel construction shell. Tubes
shall be seamless type with aluminum star
innerfins.
Tubes shall be expanded to tube plates
and shall be replaceable in the field.
The refrigerant side of the cooler shall
be cleaned, dehydrated and tested for
leakage at the maximum permissible working
pressure of 13kg/cm'2G. The waterside
of the cooler shall be tested for water
leakage at the maximum permissible working
pressure.
|